InteliLite Global Guide
231
Setpoint group Generator settings Related FW 1.9.0
Range [units]
Generator Undervoltage Wrn (page 232) .. Generator Overvoltage Sd (page 230)
[%]
Default value 110 % Alternative config NO
Step 1 % of Nominal Voltage Ph-N (page 179) or Nominal Voltage Ph-Ph (page 179)
Comm object 9686 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note: Phase to phase and phase to neutral voltages are used for this protection.
Generator Overvoltage Wrn
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.9.0
Range [units] 0 .. Generator Undervoltage Wrn (page 232) [%]
Default value 70 % Alternative config NO
Step 1 % of Nominal Voltage Ph-N (page 179) or Nominal Voltage Ph-Ph (page 179)
Comm object 8293 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is used.
Note: Phase to phase and phase to neutral voltages are used for this protection.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Generator Undervoltage BOC
6 back to List of setpoints