EasyManuals Logo

ComAp InteliLite AMF25 User Manual

ComAp InteliLite AMF25
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #223 background imageLoading...
Page #223 background image
InteliLite Global Guide
223
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 ... 1 000 [-]
Default value 1 Alternative config NO
Step 1
Comm object 10995 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only if LBI PULSE COUNTER 2 (PAGE 535) is configured
Description
This setpoint adjusts the rate of increasing of the Pulse Counter 2 function. The module counts pulses at the
input PULSE COUNTER 2 (PAGE 535) and if the input pulses counter reaches value given by this setpoint, the
counter value Pulse Counter 2 (page 470) is increased by 0,1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Conversion Coefficient Pulse 2
6 back to List of setpoints
Subgroup: Power switch
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 32 000 [kW]
Default value 100 kW Alternative config NO
Step 1 kW
Comm object 11658 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if the logical binary output POWER SWITCH (PAGE 585) is configured.
Description
Threshold level for switching the binary output POWER SWITCH (PAGE 585) on.
Image 8.15 Power Switch Level On < Level Off
Power Switch On

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals