InteliLite Global Guide
186
Setpoint group Basic settings Related FW 1.9.0
Range [units] AUTO/ECU/INTERNAL [-]
Default value AUTO Alternative config NO
Step [-]
Comm object 13345 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint selects source of running hours
AUTO If there is some ECU which send valid running hours, then this value is used.
Otherwise value from internal counter is used.
ECU Running hours are taken from ECU if ECU send valid data. It is not possible to set
and reset this value in statistics.
INTERNAL Running hours are taken from internal counter. It is possible to set and reset this value
in statistics.
Note: It is not necessary to restart controller when this setpoint is changed. Change of this setpoint
should be applied immediately.
RunHoursSource
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65