InteliLite Global Guide
251
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 9269 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT04 (PAGE 607) is configured
Description
Shutdown or BOC threshold level for AIN PROT04 (PAGE 607).
Note: These setpoints are used only if LAI AIN PROT04 (PAGE 607) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 4 Sd
6 back to List of setpoints
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 9270 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT04 (PAGE 607) is configured
Description
Delay for AIN PROT04 (PAGE 607).
Note: These setpoints are used only if LAI AIN PROT04 (PAGE 607) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 4 Delay
6 back to List of setpoints