EasyManua.ls Logo

ComAp InteliLite AMF25 - Page 251

ComAp InteliLite AMF25
774 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite Global Guide
251
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI[-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15666 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator IDMT Overcurrent protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoint IDMT
Overcurrent Delay (page 244).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 561).
IDMT Overcurrent Protection
6 back to List of setpoints
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI[-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15667 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Current Unbalance protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Current
Unbalance BOC (page 245) and Current Unbalance BOC Delay (page 245).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 561).
Current Unbalance Protection
6 back to List of setpoints

Table of Contents

Related product manuals