InteliLite Global Guide
252
Subgroup: Voltage Protection
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15668 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Generator <> Voltage protection. GCBclosing is blocked, if
the protection is disabled!
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Generator
Overvoltage Sd (page 245), Generator Overvoltage Wrn (page 246), Generator
Undervoltage BOC (page 246), Generator Undervoltage Wrn (page 247) and
Generator <> Voltage Delay (page 247).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 561).
Generator <> Voltage Protection
6 back to List of setpoints
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15669 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Voltage Unbalance protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Voltage
Unbalance BOC (page 247) and Voltage Unbalance BOC Delay (page 248).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 561).
Voltage Unbalance Protection
6 back to List of setpoints