InteliLite Global Guide
259
Setpoint group AMF settings Related FW 1.9.0
Range [units] 1 .. 150 [%] of Nominal Voltage Ph-Ph (page 195)
Default value 10 % Alternative config NO
Step 1 % of Nominal Voltage Ph-Ph (page 195)
Comm object 8446 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Operation Mode (page 199)
Description
Threshold for mains voltage unbalance.
Mains Voltage Unbalance
6 back to List of setpoints
Setpoint group AMF settings Related FW 1.9.0
Range [units] 0,0 .. 600,0 [s]
Default value 2,0 s Alternative config NO
Step 0,1 s
Comm object 8447 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Operation Mode (page 199)
Description
Delay for Mains Voltage Unbalance (page 259) protection.
Mains Voltage Unbalance Delay
6 back to List of setpoints
Subgroup: AMF Frequency Conditions
Setpoint group AMF settings Related FW 1.9.0
Range [units] Mains Underfrequency (page 260) .. 150 [%]
Default value 102,0 % Alternative config NO
Step 1,0 % of Nominal Frequency (page 196)
Comm object 8310 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Operation Mode (page 199)
Description
Threshold for mains overfrequency.
Mains Overfrequency
6 back to List of setpoints

Table of Contents