InteliLite Global Guide
278
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 9296 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT13 (PAGE 616) is configured
Description
Shutdown or BOC threshold level for AIN PROT13 (PAGE 616).
Note: These setpoints are used only if LAI AIN PROT13 (PAGE 616) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 13 Sd
6 back to List of setpoints
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 9297 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT13 (PAGE 616) is configured
Description
Delay for AIN PROT13 (PAGE 616).
Note: These setpoints are used only if LAI AIN PROT13 (PAGE 616) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 13 Delay
6 back to List of setpoints