267
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 9261 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT01 (PAGE 640) is configured
Description
Delay for AIN PROT01 (PAGE 640).
Note: These setpoints are used only if LAI AIN PROT01 (PAGE 640) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 1 Delay
6 back to List of setpoints
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 11407 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH01 (PAGE 582) is configured
Description
Threshold level for switching the binary output AIN SWITCH01 (PAGE 582) on. The value is measured from
AIN SWITCH 01 (PAGE 660) analog input.
Image 8.25 General analog input 1 switch
Analog Switch 1 On
6 back to List of setpoints