InteliLite Global Guide
269
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 9287 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT10 (PAGE 613) is configured
Description
Shutdown or BOC threshold level for AIN PROT10 (PAGE 613).
Note: These setpoints are used only if LAI AIN PROT10 (PAGE 613) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 10 Sd
6 back to List of setpoints
Setpoint group General Analog Inputs Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 9288 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT10 (PAGE 613) is configured
Description
Delay for AIN PROT10 (PAGE 613).
Note: These setpoints are used only if LAI AIN PROT10 (PAGE 613) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 10 Delay
6 back to List of setpoints