InteliLite Global Guide
261
Subgroup: AMF Settings
Setpoint group AMF settings Related FW 1.9.0
Range [units] Manual / Auto [-]
Default value Auto Alternative config NO
Step [-]
Comm object 9590 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Operation Mode (page 199)
Description
Setpoint adjust the behavior of closing MCB when the mains returns.
Manual
Controller remains in AUT mode and the manual return to Mains is done via MCB
button. Manual Restore (page 706) message is displayed in alarmlist to notify
operator - it will disappear automatically after MCB close button is pushed.
Note: Select MANUAL in case you need to manually control the moment when the
load is transferred back to the mains.
Auto No automatic mode change is performed.
Return From Island
6 back to List of setpoints
Setpoint group AMF settings Related FW 1.9.0
Range [units] Close On / Close Off [-]
Default value Close Off Alternative config NO
Step [-]
Comm object 8444 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Operation Mode (page 199)
Description
The set point influences the behavior of the output MCB CLOSE/OPEN (PAGE 614).
Close On When the output MCB CLOSE/OPEN (PAGE 614) is closed – MCB should be closed.
Close Off When the output MCB CLOSE/OPEN (PAGE 614) is closed – MCB should be opened.
MCB Logic