InteliLite Global Guide
614
LBO: M
Related FW 1.9.0 Related applications AMF
Comm object 78
Description
This output is active while mains failure is not detected and mains voltage and frequency is within limits.
This output is active when the mains voltage and frequency are within limits. The limits for under/overvoltage
and under/overfrequency are the same as for mains voltage/frequency and can be found in the Mains
Settings setpoint group.
It works only with Application Mode Select = SPTM, the output is always inactive with Application Mode
Select = MINT.
Mains Healthy
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1258
Description
This output is active when controller is in MAN mode and the engine is stopped and it is possible to start it
i.e. no red alarm is activated or SD OVERRIDE (PAGE 565) is active (Output READY (PAGE 623) is active).
Manual Ready
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF
Comm object 45
Description
The output controls the mains circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Note: InteliLite controllers can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
Image 8.189 MCB Close command
MCB Close/Open