InteliLite Global Guide
219
Setpoint group Engine settings Related FW 1.9.0
Range [units] Disabled / 1 .. 60 [s]
Default value 30 s Alternative config YES
Step 1 s
Comm object 10685 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if the logical binary output FUEL PUMP (PAGE 572) is configured
Description
If the controller does not see the fuel increase during fuel transfer within this time alarm Wrn Fuel Transfer
Failed (page 670) will be displayed and the FUEL PUMP (PAGE 572) will be turned off. Alarm Wrn Fuel
Transfer Failed (page 670) will be displayed but this alarm becomes immediately inactive and it will be
possible to delete this message by the Fault reset button. If the fault is deleted the controller will initiate the
transfer again.
Transfer Wrn Delay
6 back to List of setpoints
Subgroup: Maintenance
Setpoint group Engine settings Related FW 1.9.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1 h
Comm object 11616 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 1 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Maintenance Timer 1
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals