Setpoint group Engine settings Related FW 1.9.0
Range [units] Battery Undervoltage (page 220) .. 40,0 [V]
Default value 36,0 V Alternative config NO
Step 0,1 V
Comm object 9587 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for high battery voltage.
Battery Overvoltage
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 600 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8383 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Battery Undervoltage (page 220) and Battery Overvoltage (page 221) protection.
Battery <> Voltage Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 15 [min]
Default value 5 min Alternative config NO
Step 1 min
Comm object 11374 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Conditioned with LBI BATTERY CHARGER (PAGE 500)
Description
Delay for LBI BATTERY CHARGER (PAGE 500).
Battery Charger Fail Delay
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals