InteliLite Global Guide
588
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1372
Description
This output is closed when DPF lamp from ECU is active.
Regen Needed
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 2285
Description
Logical binary outputs which can be controlled remotely via MODBUS. There are fixed registers for
MODBUS control.
Holding register 5200 - this register can adjust all switches
supported function 6
value 0000 (all switches are 0) .. value FFFF (all switches are 1)
Single register 5210
supported function 5
value 0000 (switch is 0) / value FF00 (switch is 1)
Remote Control 01
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 2286
Description
Logical binary outputs which can be controlled remotely via MODBUS. There are fixed registers for
MODBUS control.
Holding register 5200 - this register can adjust all switches
supported function 6
value 0000 (all switches are 0) .. value FFFF (all switches are 1)
Single register 5211
supported function 5
value 0000 (switch is 0) / value FF00 (switch is 1)
Remote Control 02
6 back to Logical binary outputs alphabetically