InteliLite Global Guide
596
Related FW 1.9.0 Related applications AMF, MRS
Comm object 67
Description
The output is designed to be used as an indication that the gen-set is running. The output closes if FUEL
SOLENOID (PAGE 572) is closed and STARTER (PAGE 597) and PRESTART (PAGE 585) are open. The out
remains close until engine stop and cooling period elapses.
Image 8.184 Running
Running
6 back to Logical binary outputs alphabetically
LBO: S
Related FW 1.9.0 Related applications AMF, MRS
Comm object 962
Description
The output is closed if SD OVERRIDE (PAGE 537) input is active and open if SD OVERRIDE (PAGE 537) input is
inactive. This output is usually used to send information about SD OVERRIDE (PAGE 537) input into ECU.