InteliLite Global Guide
569
LBO: E
Related FW 1.9.0 Related applications AMF, MRS
Comm object 114
Description
This output is active when an ECU is configured, but the communication with the ECU is not established or
has dropped out.
Note: When ECU POWER RELAY (PAGE 570) is not configured, output is evaluated all the time. If ECU
POWER RELAY (PAGE 570) is configured, output is evaluated only when engine is not stop (ECU POWER
RELAY (PAGE 570) is active).
ECU Communic Error
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 347
Description
This output is active when an ECU is configured, connected and the communication with the ECU is
established.
Note: When ECU POWER RELAY (PAGE 570) is not configured, output is evaluated all the time. If ECU
POWER RELAY (PAGE 570) is configured, output is evaluated only when engine is not stop (ECU POWER
RELAY (PAGE 570) is active).
ECU Communic OK
6 back to Logical binary outputs alphabetically