InteliLite Global Guide
88
Active no shutdown alarm active,
other than OFF Mode selected
Prestart Prestart time elapsed FUEL SOLENOID (PAGE 572) on,
STARTER (PAGE 597) on, Maximum
Cranking Time (page 190) counter
started
Cranking
Cranking RPM > Starting RPM STARTER (PAGE 597) off, PRESTART
(PAGE 585) off
Starting
D+ input activated or oil pressure
detected or Generator voltage >
25% Nominal voltage
STARTER (PAGE 597) off, PRESTART
(PAGE 585) off
Cranking
Maximum Cranking Time (page
190), 1st attempt
STARTER (PAGE 597) off, FUEL
SOLENOID (PAGE 572) off, STOP
SOLENOID (PAGE 598) on, Cranking
Fail Pause (page 190) timer started
Crank
pause
Maximum Cranking Time (page
190) elapsed, last attempt
STARTER (PAGE 597) off, PRESTART
(PAGE 585) off
Shutdown
(Start fail)
Crank pause Cranking Fail Pause (page 190)
elapsed
STARTER (PAGE 597) on, FUEL
SOLENOID (PAGE 572) on, STOP
SOLENOID (PAGE 598) off, Maximum
Cranking Time (page 190) counter
started
Cranking
Starting Idle Time (page 198) elapsed Minimal Stabilization Time (page
200) and Maximal Stabilization
Time (page 201) counter started
Running
any shutdown condition FUEL SOLENOID (PAGE 572) off,
STOP SOLENOID (PAGE 598) on
Shutdown
all cranking attempts elapsed FUEL SOLENOID (PAGE 572) off,
STOP SOLENOID (PAGE 598) on
Shutdown
(Start fail)
Running Stop request READY TO LOAD (PAGE 587)
off,Cooling Time (page 203)
counter started
Cooling
RPM = 0 or any other shutdown
condition
READY TO LOAD (PAGE 587) off,
FUEL SOLENOID (PAGE 572) off
Shutdown
GCB CLOSE/OPEN (PAGE 574)
closed
Loaded
Loaded GCB CLOSE/OPEN (PAGE 574)
opened
Running
RPM = 0 or any other shutdown
condition
FUEL SOLENOID (PAGE 572) off,
STOP SOLENOID (PAGE 598) on,
READY TO LOAD (PAGE 587) off,
Shutdown
Cooling Cooling Time (page 203) elapsed FUEL SOLENOID (PAGE 572) off,
STOP SOLENOID (PAGE 598) on
Stop

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals