if the temperature measured in the room is between 22°C and 21°C; if the temperature is between 21°C and 20°C, speed level 2 will
be activated and if the temperature measured is lower than 20°C speed level 3 will be activated.
On-Board Outputs: set this option if you want to use the on-board outputs, the control relay for a climate zone (boiler or electrovalve)
and the 3 potential speed levels for the convector heater. The 3 outputs controlling the 3 convector heater speeds (50 mA / 24 Vdc)
are low-voltage and as such should be connected to a power relay.
Module + Output: set this option to control, at the temperature sensor, a boiler or electrovalve connected to a module output over the
BUS. Set the module number and the output number.
Remote valve: set this option if you want to control a multi-speed convector heater connected to a module over the BUS. In this case
the rst 4 module outputs on the installed module will be reserved for this function. Set the number of the module you wish to use and
specify which of the 3 speeds will be used.
For example, if you select "Remote valve" and set the module number to 2, output 1 on module 2 will be used for consent and
activation of the temperature control machine, while outputs 2, 3 and 4 on the same module will be used to control the 3 speed levels.
Output 2 for speed level 1, output 3 for speed level 2 and output 4 for speed level 3.
Day / Night / Empty Setpoint: select the setpoint and the zone to which the various operating modes will be applied. If a supervisor
panel such as Planux Manager or Minitouch is used, we recommend that none of these setpoints are selected.