52 Condair CRC and CRC-NA
4. Set the Condair CP3mini into operation, go to the setup level of the unit software and set the pa-
rameters "Hum.Control" to "Int.(PI)", "Controlsign." to "0-10V" (or to output signal set on CRC)
or "2-10V" (for CRC-NA) and "Hum.Setpoint" to the desired value (refer to the Condair CP3mini
installation and operation manual)
Integr.-Time:8min
Controls
Hum.Control :Int.(PI)
Controlsign.:0-10V
Hum.Setpoint:Set
SignalSource:Analog
P-Band :18%rH
Esc Set