CPS SCA Series Grid-tied PV Inverter
CPS SCA50KTL-DO/US-480
and SCA60KTL-DO/US-480
Installation and Operation Manual - Rev 3.4
CHINT POWER SYSTEMS AMERICA CO.
Revision 3.4 - January 2021

Table of Contents

Questions and Answers

  • P
    Paul MooreSep 7, 2025
    What to do if my CPS Inverter displays IsolationErr (Insulation resistance low)?
    • M
      Michael LewisSep 7, 2025
      If your CPS Inverter displays the message IsolationErr (Insulation resistance low), check the PV and ground wires: 1. Turn OFF the AC switch to disconnect from the grid. 2. Open the fuse holders to isolate the PV strings and test them with a string test set. 3. Add one PV string at a time and start up the inverter to see if the alarm occurs. 4. If no alarm, turn OFF the AC switches to disconnect from the grid, add the next string, and start up the inverter again. 5. Continue until you can find the string that triggers the alarm. Trace back the faulted string to find any leakage to Earth Ground. Note: The parameter “ISOResist” in the hidden menu can be adjusted.
  • S
    sally46Aug 22, 2025
    What to do if the 'GRID' LED is blinking on my CPS Inverter?
    • B
      Brandon SmithAug 22, 2025
      If the 'GRID' LED on your CPS Inverter is blinking, take the following steps: 1. Turn off the external AC breaker. 2. Switch the DC switch to the 'OFF' position. 3. Verify that the grid voltage is within the normal range and that the AC side cable connection is correct and securely fastened.
  • A
    aperezSep 4, 2025
    What to do if my CPS Inverter displays Protect0170 (DCI high)?
    • M
      Miss Christine HudsonSep 5, 2025
      To address a Protect0170 (DCI high) error on your CPS Inverter: 1. Increase the limit of DCImax (for example, to 400mA) to give the inverter more flexibility in handling transient conditions and voltage imbalances between grid phases. 2. If the inverter still shows the error after raising the limit, it may need to be replaced.
  • P
    pfullerSep 3, 2025
    What to do if my CPS Inverter displays Protect0110 (BUS over voltage (firmware))?
    • T
      Travis WoodsSep 3, 2025
      To address a Protect0110 (BUS over voltage (firmware)) error on your CPS Inverter: 1. Restart the inverter by turning both the AC and DC switches OFF. Wait for 1 minute for all energy to discharge, then turn both switches ON. 2. If the inverter cannot clear the fault, it may require replacement.
  • D
    dsmithSep 2, 2025
    What to do if my CPS Inverter displays Protect0090 (Bus over voltage)?
    • J
      Jessica SmithSep 2, 2025
      To address a Protect0090 (Bus over voltage) error on your CPS Inverter: 1. Restart the inverter by turning both the AC and DC switches off. Wait for one minute to allow all energy to discharge, then turn both switches on. 2. If the inverter cannot clear the fault, it may need to be replaced.
  • T
    Tina WilliamsAug 31, 2025
    What to do if my CPS Inverter displays Protect0150 (Mini MCU Fault)?
    • E
      Elizabeth AndersonAug 31, 2025
      To address a Protect0150 (Mini MCU Fault) on your CPS Inverter: 1. Restart the inverter by turning both the AC and DC switches OFF, wait for 1 minute to allow all energy to discharge, and then turn both switches ON. 2. If the inverter cannot clear the fault, it may need to be replaced.
  • A
    Amy MorrisAug 30, 2025
    What to do if my CPS Inverter displays Protect0030 (Inverter Over Current)?
    • S
      Shannon WestAug 30, 2025
      To resolve a Protect0030 (Inverter Over Current) error on your CPS Inverter: 1. Restart the inverter by turning both AC and DC switches off, waiting one minute, and then turning them back on. 2. If the fault persists, the inverter may need replacement.
  • J
    Jeremiah WalkerAug 29, 2025
    What to do if my CPS Inverter displays Protect0020 (Grid relay error)?
    • B
      Becky FisherAug 29, 2025
      To address a Protect0020 (Grid relay error) on your CPS Inverter: 1. Restart the inverter by turning both the AC and DC switches off, wait one minute, and then turn them back on. 2. If the fault persists, the inverter may need to be replaced.
  • A
    alexandra49Aug 27, 2025
    What to do if my CPS Inverter displays GFCIErr (leakage current high)?
    • A
      Angel ChapmanAug 27, 2025
      If your CPS Inverter displays a GFCIErr (leakage current high) message, check the PV and ground wires: 1. Turn OFF the AC switch to disconnect from the grid. 2. Open the fuse holders to isolate the PV strings and test them with a string test set. 3. Add one PV string at a time and start up the inverter to see if the alarm occurs. 4. If no alarm, turn OFF AC switches to disconnect from the grid and add the next string, then start the inverter again. 5. Continue until you identify the string that triggers the alarm, then trace back the faulted string to find any leakage to Earth Ground.
  • H
    hansenmelindaAug 26, 2025
    What to do if my CPS Inverter displays Warn0040 (DC SPD) error?
    • S
      Susan CamposAug 26, 2025
      To resolve a Warn0040 (DC SPD) error on your CPS Inverter: 1. Visually inspect the DC Surge Protection Device (SPD). 2. If the indicator is red, replace the SPD module. 3. If the indicator is green, remove and reinstall the SPD module in its socket. If the problem continues, further assistance may be needed.

Summary

Important Safety Instructions

Warnings and Markings on the Product

Details various safety warnings and symbols used in the manual and on the product.

Overview

Product Features

Lists the key features and specifications of the CPS SCA series inverters.

Installation

Recommendations Before Installation

Provides crucial advice and considerations before proceeding with the inverter installation.

Mechanical Installation

Guides the physical mounting of the inverter, including dimensions and methods.

Electrical Installation

Covers the wiring and electrical connections required for the inverter.

Commissioning

Mechanical Installation Check

Verifies the secure and proper mechanical installation of the inverter.

Conductor Connections Check

Ensures correct and secure electrical connections for all conductors.

Electrical Check

Confirms correct AC voltage and DC open circuit voltage before system startup.

Commissioning Steps

Outlines the sequential steps required to commission the inverter.

Main Menu and Operation

Fault Shutdown and Troubleshooting

LED Fault and Troubleshooting

Guides troubleshooting based on LED indicators, referring to tables for solutions.

LCD Fault and Troubleshooting

Provides guidance on diagnosing and resolving faults displayed on the LCD screen.

Maintenance and De-installation

Technical Data

Datasheet

Comprehensive technical specifications for the CPS SCA50KTL/60KTL inverters.

CPS SCA60KTL-DO/US-480 Specifications

General IconGeneral
BrandCPS
ModelSCA60KTL-DO/US-480
CategoryInverter
LanguageEnglish