EasyManua.ls Logo

Critical Environment Technologies FCS - Introduction; General Description; Key Features

Critical Environment Technologies FCS
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 © 2021 All rights reserved. Data subject to change without notice.
FCS - Installation Manual Rev. C | 2021.12
2 INTRODUCTION
2.1 General Description
NOTE: The FCS Installation Manual outlines the basic features and functionality of the FCS
and includes information about installing and wiring the system. If you require more in
depth information about how the FCS can be congured (channels, relays, strobe/audible
and analog input and output settings), using passcodes, logic and priority settings and the
Modbus® holding registers, please download the FCS Operation Manual from our website.
Thank you for purchasing our FSC Flexible Control System. The FCS Flexible Control System
is a sophisticated, high performance controller that offers multi-channel congurations for
monitoring toxic, combustible and refrigerant gases with versatile control functionality for
non-hazardous, non-explosion rated, commercial and light industrial applications. The FCS is
designed to accept inputs from digital and/or analog transmitters and/or Peripheral Devices
(in various combinations), using Modbus® RTU RS-485 or 4-20 mA analog input.
The FCS is available in 4 channel, 8 channel, 32 channel and 128 channel models with
either Modbus® RTU RS-485 WAN output or with BACnet® MS/TP RS-485 WAN output for
communicating with a Building Automation System (BAS).
All models include, four congurable SPDT dry contact relays with eld congurable time
delays and trigger levels, a full colour LCD resistive touch screen with LED panel indicating
congurable channel alarm status, relay status and fault conditions, extensive menu system
with password protection, enhanced logic control, priorities/zoning capabilities, a USB port
for rmware upgrades, data logging and a door-mounted, audible alarm. The FCS has exible
conguration settings for analog outputs and supports 4-20 mA and Modbus® driven VFDs.
2.2 Key Features
A 1/4 VGA full colour, resistive touch LCD display with an LED panel for alarm status
fault conditions
Extensive menu system with password protection
Has a USB port for in the eld rmware upgrades and data logging downloads
Congured with either a Modbus® RTU RS-485 or a BACnet® MS/TP RS-485 digital
output signal for WAN communications (for communicating with a BAS)
Supports Modbus® driven VFDs
Flexible conguration of analog outputs
Enhanced logic control, zoning and priority structure capabilities
With the optional Analog Output board(s) (Option -AO or -2AO) installed, the FCS can
be congured to have up to 8 internal 4-20 mA outputs* for VFD control or usable by
any other device requiring a signal representing the levels of gases detected
With the optional Analog Input board(s) (Option -AI or -2AI) installed, the FCS can be
congured to have up to 8 internal analog inputs*
A door mounted, loud audible alarm that is ideal for noisy environments.
Four 5-amp SPDT dry contact relays with eld congurable time delays and trigger
levels

Table of Contents