2 9 J A N U A R Y 2 0 1 3 D R A F T
7 — DIAGNOSTICS & TROUBLESHOOTING
Table 6 TROUBLESHOOTING CHART, continued
FLASH SUB
CLEAR STEER TRACTION
CODE CODE
NAME
POSSIBLE CAUSE
SET CONDITION
CONDITION
FAULT ACTION
FAULT ACTION
39 1 Contactor 1. Steer contactor was closed temporarily, The steer contactor was closed, but detected Cycle KSI. Warning then 1 = Stop.
Opened but then opened. open. This fault is set only when Contactor Shutdown.
2. Steer contactor tips are oxidized. Control Type = 1 and Checks Enable = On.
3. An external load on the capacitor In Contactor State = 2 (Closed), the fault
bank (B+ terminal) that prevents will be set if the capacitor bank and
the bank from charging. keyswitch voltages differ by more than 5 V.
39 2
Contactor 1. Steer contactor did not close. The steer contactor did not close when Cycle KSI. Shutdown. 1 = Stop.
Did Not Close 2. Steer contactor tips are oxidized. commanded. This fault is set only when
3. An external load on the capacitor Contactor Control Type = 1 and Checks
bank (B+ terminal) that prevents Enable = On. In Contactor State = 1
the bank from charging. (Closing), the fault will be set if the
capacitor bank and keyswitch voltages
differ by more than 2 V.
41 1
Command Command input device’s Analog 3 input Analog1 voltage > Analog1 Fault Max Cycle KSI. Hold then 1 = Stop.
Analog1 (pin 8) is out of range. or Analog1 voltage < Analog1 Fault Min. Shutdown.
Out of Range The fault is checked only if Command
Input Device = 0, 2, or 3.
42 1
Command Command input device’s Analog 3 input Analog3 voltage > Analog3 Fault Max Cycle KSI. Hold then 1 = Stop.
Analog3 (pin 19) is out of range. or Analog3 voltage < Analog3 Fault Min. Shutdown.
Out of Range The fault is checked only if Command
Input Device = 0, 2, or 3.
43 1 Feedback
Position feedback device’s Analog 5 input Analog5 voltage > Analog5 Fault Max Cycle KSI. Hold then 1 = Stop.
Analog5 (pin 16) is out of range. or Analog5 voltage < Analog5 Fault Min. Shutdown.
Out of Range The fault is checked only if Position
Feedback Device = 0, 2, or 3.
44 1 Feedback
Position feedback device’s Analog 6 input Analog6 voltage > Analog6 Fault Max Cycle KSI. Hold then 1 = Stop.
Analog6 (pin 17) is out of range. or Analog6 voltage < Analog6 Fault Min. Shutdown.
Out of Range The fault is checked only if Position
Feedback Device = 0, 2, or 3.
45 1
CAN Not 1222 CAN NMT State did not go This check is made only when the parameter Cycle KSI. Warning and 1 = Stop.
Operational operational within 80 ms of interlock CAN Required = On. With Interlock = On drop fault
being applied. for 80 ms, the CAN NMT State is <> output.
Operational.