EasyManua.ls Logo

Daikin AVV - Page 24

Daikin AVV
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 817-7 24 www.DaikinApplied.com
Figure 69: 2-Way EOC Valve Dimensions
Connection Cv X Y Z
3/4" (19mm)
FNPT
7.5
1
11
/16"
(43mm)
15
/16" (24mm) 3⅝" (92mm)
3-Way End of Cylce Valve
When piping the 3-Way End of Cycle valve, refer to label
to determine the direction of ow. The valve should be
installed so that there is a 2” (51mm) minimum clearance
to remove the actuator from the valve body. Provide
unions for removal of unit coil and/or control valve as
a future service consideration. Hot water connections
may be same end as cooling coil connections, but are
recommended to be opposite end to facilitate piping.
When using MicroTech® controls, they must be opposite
end. The End of Cycle valve accessory must be eld
installed on the unit for which it was selected.
Figure 70: 3-Way EOC Valve Dimensions
Connection Cv Y
3/4" (19mm)
FNPT
5.0
15
/16" (24mm)
Figure 71: 2-Way EOC Steam Valve Dimensions
Connection Cv X Y Z
1" (25mm) FNPT 8.0 1⅞" (47mm) 1" (25mm) 3
11
/16" (94mm)
Table 10: EOC Actuator Specifications
Control 2 Position
Electrical 24 VAC, 50/60 Hz
Stroke
Power Stroke 9 to 11 seconds
Spring return 4 to 5 seconds
Ambient 32°F to 125°F (0°C to 52°C)
Table 11: F&BP EOC Valve Body Specifications
2-Way Valve 3-Way Valve
Connections 3/4" FNPT, 1" FNPT 3/4" FNPT
Static Pressure 300 psi (2100 kPa) 300 psi (2100 kPa)
Close-Off Pressure
13 & 15 psi
(90 & 103 kPa)
13 psi (90 kPa)
Temperature
32°F to 200°F
(0°C to 93°C)
32°F to 200°F
(0°C to 93°C)

Table of Contents

Related product manuals