EasyManua.ls Logo

Daikin AVV - Cooling - Chilled Water Modulating; Valve Piping

Daikin AVV
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.DaikinApplied.com 35 IM 817-7
Cooling – Chilled Water Modulating
Valve Piping
2-way Modulating, Normally Closed,
Chilled Water Valve Piping (typical)
The 2-way Modulating chilled water valve is furnished
normally closed to the coil. When the valve is de-energized
(off) there is no ow through the coil. Energizing the valve
allows ow through the coil in a modulating fashion.
CAUTION
Refer to the arrow on the modulating valve body to determine the
direction of ow. If the valve is mounted improperly, the unit will
not operate properly and damage to the valve may result.
Figure 90: 2-Way Modulating Valve Control, Normally
Closed, Chilled Water Piping
Return
Return
Balancing and Shutoff Valve
Shutoff Valve
Supply
Supply
2-way Modu-
lating
Valve
Unit Coil
Unions
Figure 91: 2-Way Modulating, Normally Closed Chilled
Water Valve Piping
3-Way Modulating, Normally Closed,
Chilled Water Valve Piping (typical)
The 3-way Modulating chilled water valve is furnished
normally closed to the coil. When the valve is de-
energized (off) the ow bypasses the coil. Energizing the
valve allows ow through the coil in a modulating fashion.
Figure 92: 3-Way Modulating Valve Control, Normally
Closed, Chilled Water Piping
Return
Shutoff Valve
Supply
Supply
3-way
Modulating
Valve
Union
Balancing Valve
N.C.
N.O.
Return
Unit Coil
Union
Common
Balancing and Shutoff Valve

Table of Contents

Related product manuals