www.DaikinApplied.com 25 IM 817-7
2-Way Modulating Valve (Chilled Water,
Hot Water or Combination)
Two-way modulating control valves for MicroTech are
designed to regulate the ow of chilled water, hot water
or the combination. They consist of a nickel plated brass
body and stainless steel ball valve and stem, with a
spring return proportional actuator. The optional valve
accessory is shipped separate from the unit ventilator
for eld installation to prevent shipping damage and to
provide exibility in making the eld piping connection.
Figure 72: 2-Way Modulating Valve Dimensions
B
A
D
C
E F
AB
A
Table 12: 2-Way Actuator Specifications (CW, HW, CW/HW)
Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%
Electrical Connection
3ft [1m], 18 GA plenum cable with 1/2”
conduit connector
Overload Protection electronic throughout 0° to 95° rotation
Operating Range Y
2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500
Ω, 1/4 W resistor)
Input Impedance
100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω
for 4 to 20 mA
Feedback Output U 2 to 10 VDC, 0.5 mA max
Angle of Rotation Max. 95°, 90°
Position Indication
visual indicator, 0° to 95° (0° is full spring
return position)
Running Time (Motor) 95 sec
Running Time (Fail-Safe) <25 sec
Ambient Humidity max. 95% RH non-condensing
Ambient Temperature Range -22°F to 122°F [-30°C to 50°C]
Storage Temperature Range -40°F to 176°F [-40°C to 80°C]
Table 13: 2-Way Valve Body Specifications (CW, HW, CW/HW)
Service chilled, hot water, up to 60% glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
Body Pressure Rating [psi] 600
Media Temperature Range
(Water)
0°F to 250°F [-18°C to 120°C]
Max Differential Pressure
(Water)
50 psi (345 kPa)
Close-Off Pressure 200 psi
Table 14: 2-Way Modulating Valve 1/2″ – Dimensions (CW, HW, CW/HW)
Valve Part No. Cv
Connection Size
(inches)
A B C D E F
B209 0.8
1/2"
6.59" (167mm) 2.38" (60mm) 4.9" (124mm) 4.32" (110mm) 1.53" (38mm)B210 1.2
B211 1.9
B212 3.0
6.59" (167mm) 2.38" (60mm) 5.48" (139mm) 4.71" (120mm) 1.53" (38mm)B213 4.7
B214 7.4
Table 15: 2-Way Modulating Water Valve 1/2″ – Pressure Drop (CW, HW, CW/HW)
Pressure Drop Across the Valve
2-Way CCV
Part No.
Cv
Maximum
Rating
Connection Size 1 PSI 2 PSI 3 PSI 4 PSI 5 PSI 6 PSI 7 PSI 8 PSI 9 PSI 10 PSI
B209 0.8
1/2"
0.8 1.1 1.4 1.6 1.8 2.0 2.1 2.3 2.4 2.5
B210 1.2 1.2 1.7 2.1 2.4 2.8 2.9 3.2 3.4 3.6 3.8
B211 1.9 1.9 2.7 3.3 3.8 4.2 4.7 5.0 5.4 5.7 6.0
B212 3.0 3.0 4.2 5.2 6.0 6.8 7.3 7.9 8.5 9.0 9.5
B213 4.7 4.7 6.6 8.1 9.4 11 12 12 13 14 15
B214 7.4
7.4 10 13 15 17 18 20 21 22 23

Table of Contents