EasyManuals Logo
Home>Danfoss>Measuring Instruments>AK-SM 350

Danfoss AK-SM 350 User Manual

Danfoss AK-SM 350
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
AK-SM 350 Version 1.7x Manual RS8EF402 © Danfoss 02-2009 33
Tidy up the alarms
This function deletes all the active alarms. You use this function
at the start-up of a new plant for which you want to update the
alarms that are always active (after activation all the active alarms
will be regenerated).
Clearing the alarm history
Only use this function when no alarms are active.
This function deletes all alarms that were previously triggered.
Also those are currently active.
Reset the list by pressing Enter.
Test of alarm function
This function is used to check whether an alarm route and an
alarm destination are correctly configured.
When "On" is activated, a test alarm will be generated with the
alarm priority set for the next function.
Repeat the test with the other alarm priorities.
When the test is complete, the function should be set to "O".
Alarm priority to be tested
In addition to the settings shown, "Log only" and "Disabled" are
also available.
"I'm alive alarm"
This function will send an "I’m alive alarm" to the alarm destina-
tion. The alarm is sent at fixed intervals, and if it fails to arrive at
the alarm destination the monitoring unit will indicate that there
is a problem.
Interval for "I'm alive alarm"
Set time interval.
Alarm routes
This is where you set how the alarms are to be routed.
The description selects an alarm route. This route sends alarms to
"Destination 1" at the stores opening time and to "Destination 2"
at the stores closing time.
This setup is displayed so that all alarms are handled at the same
time. If you want to distinguish important alarms from each other,
you must create several alarm routes. This means each alarm route
can handle its own alarm priority.
Mode
Select "Enabled"
Alarm priority
This is where you set which alarms are to be sent along this route.
In this example, "All" is selected.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-SM 350 and is the answer not in the manual?

Danfoss AK-SM 350 Specifications

General IconGeneral
BrandDanfoss
ModelAK-SM 350
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals