EasyManua.ls Logo

Danfoss FC 300

Danfoss FC 300
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-41 Motor Angle Offset
Range: Function:
0
*
[0 - 65535] Enter the correct offset angle between the PM motor and the
index position (single-turn) of the attached encoder or resolver.
The value range of 0 – 65535 corresponds to 0 - 2 * pi (radians).
To obtain the offset angle value: After drive start-up apply DC-
hold and enter the value of par. 16-20
Motor Angle
into this
parameter.
This parameter is only active when par. 1-10
Motor construc-
tion
is set to
PM, non-salient SPM
[1] (Permanent Magnet Mo-
tor).
2.4.5. 1-5* Load Indep. Setting
Parameters for setting the load-independent motor settings.
1-50 Motor Magnetisation at Zero Speed
Range: Function:
100% [0 - 300 %] Use this par. along with par. 1-51
Min Speed Normal Magnetis-
ing [RPM]
to obtain a different thermal load on the motor when
running at low speed.
Enter a value which is a percentage of the rated magnetizing
current. If the setting is too low, the torque on the motor shaft
may be reduced.
1-51 Min Speed Normal Magnetising [RPM]
Range: Function:
15
RPM
*
[10 - 300 RPM] Set the required speed for normal magnetising current. If the
speed is set lower than the motor slip speed, par. 1-50
Motor
Magnetisation at Zero Speed
and par. 1-51 are of no signifi-
cance.
Use this par. along with par. 1-50. See drawing for par. 1-50.
1-52 Min Speed Normal Magnetising [Hz]
Option: Function:
[Size re-
lated]
0 - 250 Hz Set the required frequency for normal magnetising current. If
the frequency is set lower than the motor slip frequency, par.
1-50
Motor Magnetisation at Zero Speed
is inactive.
Use this par. along with par. 1-50. See drawing for par. 1-50.
2. How to Programme FC 300 Programming Guide
50
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss FC 300

Related product manuals