EasyManuals Logo

Danfoss FC 300 Manual

Danfoss FC 300
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
FC 300 CANopen
- P a r a m e t e r s -
46 MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
- Output frequency = JOG freq.: The motor runs at
JOG frequency until communication resumes.
- Output frequency = Max. freq.. The motor runs at
maximum frequency until communication
resumes.
- Stop with trip: The motor stops. You need to reset
the frequency converter, see explanation above.
Select set-up x:
This type of time-out function is used for
changing set-up on a control word time-out. If
communication resumes causing the time-out
situation to disappear, par. 8-05 End-of-time-out
Function defines whether to resume the set-up
used before the time-out or to hold the set-up
endorsed by the time-out function.
Note that the following parameters have to be
configured for the set-up change to occur on a
time-out. Par. 0-10 Active set-up has to be set to
Multi set-up along with the relevant linking set in
par. 0-12 This Set-up Linked To.
8-05 End-of-timeout Function
Option:
*Hold set-up [0]
Resume set-up [1]
Function:
Defines the action after receiving a valid control
word upon a time-out. This only applies if set-up
1-4 has been selected in par. 8-04.
Hold: The drive holds the set-up selected in par. 8-
04 and displays a warning, until par. 8-06
toggles. Then the drive resumes its original set-
up.
Resume: The drive resumes the original set-up.
8-06 Reset Control Word Timeout
Option:
*Do not reset [0]
Do reset [1]
Function:
Used for returning the drive to the original set-up
after a Control word timeout.
After setting the value to “Do Reset”[1], it returns
to “Do not reset”[0].
8-07 DiagnosisTrigger
Option:
*Disable [0]
Trigger on alarms [1]
Trigger alarms/warn. [2]
Function:
This parameter has no function for CANopen.
8-10 Control Word Profile
Option:
*FC profile [0]
CANopen DSP 402 [5]
Function:
Selects the interpretation of the control and
status words. The installed option in slot A
determines the valid selection.
8-50 Coasting Select
Option:
Digital input [0]
Bus [1]
Logic AND [2]
*Logic OR [3]
Function:
Allows a choice between controlling the coasting
function via the terminals (digital input) and/ or
via the bus.
NB! This parameter is active only when
par. 8-01 Control site is set to [0] Digital and
control word.
8-51 Quick Stop Select
Option:
Digital input [0]
Bus [1]
Logic AND [2]
*Logic OR [3]
Function:
Allows a choice between controlling the Quick
Stop function via the terminals (digital input)
and/or via the bus.
NB! This parameter is active only when
parameter 8-01 Control site is set to [0]
Digital and control word.
8-52 DC brake select
Option:
Digital input [0]
Bus [1]
Logic AND [2]
*Logic OR [3]
Function:
Allows a choice between controlling the DC brake
via the terminals (digital input) and/or via the
bus.
NB! This parameter is active only when
par. 8-01 Control site is set to [0] Digital and
control word.
8-53 Start Select

Table of Contents

Other manuals for Danfoss FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 and is the answer not in the manual?

Danfoss FC 300 Specifications

General IconGeneral
EnclosureIP20
ApprovalscUL, UL, CE
EMC filterBuilt-in
Communication OptionsCANopen, PROFIBUS DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Output Voltage0-100% of supply voltage

Related product manuals