Page #146 background imageLoading...
Page #146 background image
VLT
®
5000 FLUX
Bookstyle and Compact, Mains supply
3 x 380 - 500 V
According to international requirements VLT type 5001 5002 5003 5004
Output current I
VLT,N
[A] (380-440 V) 2.2 2.8 4.1 5.6
I
VLT, MAX
(60 s) [A] (380-440 V) 3.5 4.5 6.5 9
I
VLT,N
[A] (441-500 V) 1.9 2.6 3.4 4.8
I
VLT, MAX
(60 s) [A] (441-500 V) 3 4.2 5.5 7.7
Output S
VLT,N
[kVA] (380-440 V) 1.7 2.1 3.1 4.3
S
VLT,N
[kVA] (441-500 V) 1.6 2.3 2.9 4.2
Typical shaft output P
VLT,N
[kW] 0.75 1.1 1.5 2.2
Typical shaft output P
VLT,N
[HP] 1 1.5 2 3
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2
)
4/10 4/10 4/10 4/10
Rated input current I
L,N
[A] (380 V) 2.3 2.6 3.8 5.3
I
L,N
[A] (460 V) 1.9 2.5 3.4 4.8
Max. cable cross-section, power [mm
2
]/[AWG]
2)
4/10 4/10 4/10 4/10
Max. pre-fuses [-]/UL
1)
[A] 16/6 16/6 16/10 16/10
Efficiency
3)
0.96 0.96 0.96 0.96
Weight IP 20 EB Bookstyle [kg] 7 7 7 7.5
Weight IP 20 EB Compact [kg] 8 8 8 8.5
Weight IP 54 Compact [kg] 11.5 11.5 11.5 12
Power loss at max. load [W] 55 67 92 110
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
MG.55.A6.02 - VLT is a registered Danfoss trademark
146

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 FLUX and is the answer not in the manual?

Danfoss VLT 5000 FLUX Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 FLUX
CategoryDC Drives
LanguageEnglish

Related product manuals