VLT
®
5000 FLUX
Compact, Mains supply 3 x 380 - 500 V
According to international requirements VLT type 5016 5022 5027
Normal overload torque (110 %):
Output current I
VLT,N
[A] (380-440 V) 32 37.5 44
I
VLT, MAX
(60 s) [A] (380-440 V) 35.2 41.3 48.4
I
VLT,N
[A] (441-500 V) 27.9 34 41.4
I
VLT, MAX
(60 s) [A] (441-500 V) 30.7 37.4 45.5
Output S
VLT,N
[kVA] (380-440 V) 24.4 28.6 33.5
S
VLT,N
[kVA] (441-500 V) 24.2 29.4 35.8
Typical shaft output P
VLT,N
[kW] 15 18.5 22
Typical shaft output P
VLT,N
[HP] 20 25 30
High overload torque (160 %):
Output current I
VLT,N
[A] (380-440 V) 24 32 37.5
I
VLT, MAX
(60 s) [A] (380-440 V) 38.4 51.2 60
I
VLT,N
[A] (441-500 V) 21.7 27.9 34
I
VLT, MAX
(60 s) [A] (441-500 V) 34.7 44.6 54.4
Output S
VLT,N
[kVA] (380-440 V) 18.3 24.4 28.6
S
VLT,N
[kVA] (441-500 V) 18.8 24.2 29.4
Typical shaft output P
VLT,N
[kW] 11 15 18.5
Typical shaft output P
VLT,N
[HP] 15 20 25
Max. cable cross-section to motor, IP 54 16/6 16/6 16/6
brake and loadsharing [mm
2
]/[AWG]
2)
IP 20 16/6 16/6 35/2
Min. cable cross-section to motor,
brake and loadsharing [mm2]/[AWG]
2) 4)
10/8 10/8 10/8
Rated input current I
L,N
[A] (380 V) 32 37.5 44
I
L,N
[A] (460 V) 27.6 34 41
Max. cable cross-section, IP 54 16/6 16/6 16/6
power [mm
2
]/[AWG] IP 20 16/6 16/6 35/2
Max. pre-fuses [-]/UL
1)
[A] 63/40 63/50 63/60
Efficiency
3)
0.96 0.96 0.96
Weight IP 20 EB [kg] 21 22 27
Weight IP 54 [kg] 41 41 42
Power loss at max. load.
- high overload torque (160 %) [W] 419 559 655
- normal overload torque (110 %) [W] 559 655 768
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to com
ply with IP 20. Always comply with national and
local regulations on min. cable cross-section.
MG.55.A6.02 - VLT is a registered Danfoss trademark