EasyManuals Logo

Danfoss VLT AutomationDrive User Manual

Danfoss VLT AutomationDrive
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
Do not ground one frequency converter to another
in a “daisy chain” fashion
Keep the ground wire connections as short as
possible
Use of high-strand wire to reduce electrical noise is
recommended
Follow motor manufacturer wiring requirements
2.4.2.1 Leakage Current (>3,5mA)
Follow national and local codes regarding protective
earthing of equipment with a leakage current > 3,5mA.
Frequency converter technology implies high frequency
switching at high power. This will generate a leakage current
in the earth connection. A fault current in the frequency
converter at the output power terminals might contain a DC
component which can charge the filter capacitors and cause
a transient earth current. The earth leakage current depends
on various system configurations including RFI filtering,
screened motor cables, and frequency converter power.
EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3,5mA.
Earth grounding must be reinforced in one of the following
ways:
Earth ground wire of at least 10mm
2
Two separate earth ground wires both complying
with the dimensioning rules
See EN 60364-5-54 § 543.7 for further information.
Using RCDs
Where residual current devices (RCDs), also known as earth
leakage circuit breakers (ELCBs), are used, comply with the
following:
Use RCDs of type B only which are capable of
detecting AC and DC currents
Use RCDs with an inrush delay to prevent faults
due to transient earth currents
Dimension RCDs according to the system configu-
ration and environmental considerations
2.4.2.2 Grounding Using Shielded Cable
Earthing (grounding) clamps are provided for motor wiring
(see Illustration 2.7).
Illustration 2.7 Grounding with Shielded Cable
2.4.3 Motor Connection
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple frequency converters
separately. Induced voltage from output motor cables run
together can charge equipment capacitors even with the
equipment turned off and locked out. Failure to run output
motor cables separately could result in death or serious
injury.
For maximum wire sizes see 10.1 Power-dependent
Specifications
Comply with local and national electrical codes for
cable sizes
Motor wiring knockouts or access panels are
provided at the base of IP21 and higher
(NEMA1/12) units
Do not install power factor correction capacitors
between the frequency converter and the motor
Do not wire a starting or pole-changing device
between the frequency converter and the motor
Connect the 3-phase motor wiring to terminals 96
(U), 97 (V), and 98 (W)
Ground the cable in accordance with grounding
instructions provided
Torque terminals in accordance with the
information provided in 10.4.1 Connection
Tightening Torques
Installation
VLT
®
AutomationDrive Operating
Instructions
MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark 13
2
2

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals