Recommended max. fuse
FC 302
[kW]
Max.
prefuse
Bussmann
E52273
RK1/JDDZ
Bussmann
E4273
J/JDDZ
Bussmann
E4273
T/JDDZ
SIBA
E180276
RK1/JDDZ
LittelFuse
E81895
RK1/JDDZ
Ferraz-
Shawmut
E163267/E2137
RK1/JDDZ
Ferraz-
Shawmut
E2137
J/HSJ
11 30 A KTS-R-30 JKS-30 JKJS-30 5017906-030 KLS-R-030 A6K-30-R HST-30
15-18.5 45 A KTS-R-45 JKS-45 JJS-45 5014006-050 KLS-R-045 A6K-45-R HST-45
22 60 A KTS-R-60 JKS-60 JJS-60 5014006-063 KLS-R-060 A6K-60-R HST-60
30 80 A KTS-R-80 JKS-80 JJS-80 5014006-080 KLS-R-075 A6K-80-R HST-80
37 90 A KTS-R-90 JKS-90 JJS-90 5014006-100 KLS-R-090 A6K-90-R HST-90
45 100 A KTS-R-100 JKS-100 JJS-100 5014006-100 KLS-R-100 A6K-100-R HST-100
55 125 A KTS-R-125 JKS-125 JJS-125 2028220-125 KLS-150 A6K-125-R HST-125
75 150 A KTS-R-150 JKS-150 JJS-150 2028220-150 KLS-175 A6K-150-R HST-150
* UL compliance only 525-600 V
Table 10.13 525-690V*, Frame Sizes B and C
10.4 Connection Tightening Torques
Power (kW) Torque (Nm)
Enclo-
sure
200-240V 380-480/500V 525-600V 525-690V Mains Motor
DC
connection
Brake Earth Relay
A2 0.25 - 2.2 0.37 - 4.0 1.8 1.8 1.8 1.8 3 0.6
A3 3.0 - 3.7 5.5 - 7.5 0.75 - 7.5 1.8 1.8 1.8 1.8 3 0.6
A4 0.25 - 2.2 0.37 - 4.0 1.8 1.8 1.8 1.8 3 0.6
A5 0.25 - 3.7 0.37 - 7.5 0.75 - 7.5 1.8 1.8 1.8 1.8 3 0.6
B1 5.5 - 7.5 11 - 15 11 - 15 1.8 1.8 1.5 1.5 3 0.6
B2 11
18
22
18
22
11
22
4.5
4.5
4.5
4.5
3.7
3.7
3.7
3.7
3
3
0.6
0.6
B3 5.5 - 7.5 11 - 15 11 - 15 1.8 1.8 1.8 1.8 3 0.6
B4 11 - 15 18 - 30 18 - 30 4.5 4.5 4.5 4.5 3 0.6
C1 15 - 22 30 - 45 30 - 45 10 10 10 10 3 0.6
C2 30 - 37 55 - 75 55 - 75 30 - 75
14/24
1)
14/24
1)
14 14 3 0.6
C3 18 - 22 37 - 45 37 - 45 10 10 10 10 3 0.6
C4 30 - 37 55 - 75 55 - 75
14/24
1)
14/24
1)
14 14 3 0.6
Table 10.14 Tightening of Terminals
1)
For different cable dimensions x/y, where x 95mm
2
and y 95mm
2
.
Specifications
VLT
®
AutomationDrive Operating
Instructions
84 MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
100

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)