4.2.1 Uploading Data to the LCP
1. Press [OFF] to stop the motor before uploading or
downloading data.
2. Go to 0-50 LCP Copy.
3. Press [OK].
4. Select All to LCP.
5. Press [OK]. A progress bar shows the uploading
process.
6. Press [Hand On] or [Auto On] to return to normal
operation.
4.2.2 Downloading Data from the LCP
1. Press [OFF] to stop the motor before uploading or
downloading data.
2. Go to 0-50 LCP Copy.
3. Press [OK].
4. Select All from LCP.
5. Press [OK]. A progress bar shows the downloading
process.
6. Press [Hand On] or [Auto On] to return to normal
operation.
4.3 Restoring Default Settings
CAUTION
Initialisation restores the unit to factory default settings. Any
programming, motor data, localization, and monitoring
records will be lost. Uploading data to the LCP provides a
backup prior to initialisation.
Restoring the frequency converter parameter settings back
to default values is done by initialisation of the frequency
converter. Initialisation can be through 14-22 Operation Mode
or manually.
Initialisation using 14-22 Operation Mode does not
change frequency converter data such as operating
hours, serial communication selections, personal
menu settings, fault log, alarm log, and other
monitoring functions
Using 14-22 Operation Mode is generally
recommended
Manual initialisation erases all motor,
programming, localization, and monitoring data
and restores factory default settings
4.3.1 Recommended Initialisation
1. Press [Main Menu] twice to access parameters.
2. Scroll to 14-22 Operation Mode.
3. Press [OK].
4. Scroll to Initialisation.
5. Press [OK].
6. Remove power to the unit and wait for the display
to turn off.
7. Apply power to the unit.
Default parameter settings are restored during start up. This
may take slightly longer than normal.
8. Alarm 80 is displayed.
9. Press [Reset] to return to operation mode.
4.3.2 Manual Initialisation
1. Remove power to the unit and wait for the display
to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
Factory default parameter settings are restored during start
up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information
15-00 Operating Hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
User Interface
VLT
®
AutomationDrive Operating
Instructions
30 MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
4
4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)