Fuses or Circuit Breakers are mandatory to comply with IEC 60364. Danfoss recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V, or
600V depending on the frequency converter voltage rating. With the proper fusing the frequency converter short circuit current
rating (SCCR) is 100,000 Arms.
Enclosure FC 300 Power Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level
Size [kW] Moeller [A]
A1 0.25-1.5 gG-10 gG-25 PKZM0-16 16
A2 0.25-2.2 gG-10 (0.25-1.5)
gG-16 (2.2)
gG-25 PKZM0-25 25
A3 3.0-3.7 gG-16 (3)
gG-20 (3.7)
gG-32 PKZM0-25 25
B3 5.5 gG-25 gG-63 PKZM4-50 50
B4 7.5-15 gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-125 NZMB1-A100 100
C3 18.5-22 gG-80 (18.5)
aR-125 (22)
gG-150 (18.5)
aR-160 (22)
NZMB2-A200 150
C4 30-37 aR-160 (30)
aR-200 (37)
aR-200 (30)
aR-250 (37)
NZMB2-A250 250
A4 0.25-2.2 gG-10 (0.25-1.5)
gG-16 (2.2)
gG-32 PKZM0-25 25
A5 0.25-3.7 gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
gG-32 PKZM0-25 25
B1 5.5-7.5 gG-25 (5.5)
gG-32 (7.5)
gG-80 PKZM4-63 63
B2 11 gG-50 gG-100 NZMB1-A100 100
C1 15-22 gG-63 (15)
gG-80 (18.5)
gG-100 (22)
gG-160 (15-18.5)
aR-160 (22)
NZMB2-A200 160
C2 30-37 aR-160 (30)
aR-200 (37)
aR-200 (30)
aR-250 (37)
NZMB2-A250 250
Table 10.1 200-240V, Frame Sizes A, B, and C
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark 77
10 1
0

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)