EasyManuals Logo

Danfoss VLT AutomationDrive User Manual

Danfoss VLT AutomationDrive
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
Mains Supply 3 x 525- 690V AC
FC 302 P30K P37K P45K P55K P75K
High/ Normal Load* HO NO HO NO HO NO HO NO HO NO
Typical Shaft output at 550V
[kW]
22 30 30 37 37 45 45 55 55 75
Typical Shaft output at 575V
[HP]
30 40 40 50 50 60 60 75 75 100
Typical Shaft output at 690V
[kW]
30 37 37 45 45 55 55 75 75 90
Enclosure IP21, 55 C2 C2 C2 C2 C2
Output current
Continuous
(3 x 525-550V) [A]
36 43 43 54 54 65 65 87 87 105
Intermittent (60 sec
overload)
(3 x 525-550V) [A]
54 47.3 64.5 59.4 81 71.5 97.5 95.7 130.5 115.5
Continuous
(3 x 551-690V) [A]
34 41 41 52 52 62 62 83 83 100
Intermittent (60 sec
overload)
(3 x 551-690V) [A]
51 45.1 61.5 57.2 78 68.2 93 91.3 124.5 110
Continuous KVA
(at 550V) [KVA]
34.3 41.0 41.0 51.4 51.4 61.9 61.9 82.9 82.9 100.0
Continuous KVA
(at 575V) [KVA]
33.9 40.8 40.8 51.8 51.8 61.7 61.7 82.7 82.7 99.6
Continuous KVA
(at 690V) [KVA]
40.6 49.0 49.0 62.1 62.1 74.1 74.1 99.2 99.2 119.5
Max. input current
Continuous
(at 550V) [A]
36 49 49 59 59 71 71 87 87 99
Continuous
(at 575V) [A]
54 53.9 72 64.9 87 78.1 105 95.7 129 108.9
Additional specifications
Max. cable size, mains,
motor, load share and brake
[mm
2
(AWG)]
95 (4/0)
Estimated power loss
at rated max. load [W]
4)
480 592 720 880 1200
Weight,
enclosure IP21, IP55 [kg]
65
Efficiency
4)
0.98 0.98 0.98 0.98 0.98
For fuse ratings, see 10.3.1 Fuses
1) High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety
in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the
power loss in the frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W
to the losses. (Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed
for (+/-5%).
Specifications
VLT
®
AutomationDrive Operating
Instructions
70 MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
100

Table of Contents

Other manuals for Danfoss VLT AutomationDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive and is the answer not in the manual?

Danfoss VLT AutomationDrive Specifications

General IconGeneral
Supply Voltage3 x 200-240 V ±10% 3 x 380-500 V ±10% 3 x 525-600 V ±10%
EnclosureIP20
Output Power Range0.25 kW - 1.5 MW
Communication ProtocolsModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit, Ground fault, Motor overload
Ambient Temperature Range-10°C to +50°C (14°F to 122°F)

Related product manuals