FC 302 - Mains: 525-690V (T7) - 40% Duty Cycle
FC 302 P
m
(HO)
R
min
R
br. nom
R
rec
P
br avg
Order no. Period Cable cross
section
Therm.
Relay
Max. brake
torque with
R
rec
*
T7 [kW]
[Ω] [Ω] [Ω]
[kW] 130Bxxxx [s] [mm2] [A] [%]
P37K 37 18 23.5 22 28 2118 600 6 35 150 (150)
P45K 45 13.5 19.3 18 33 2119 600 10 42 150 (150)
P55K 55 13.5 15.8 15 42 2120 600 16 52 150 (150)
P75K 75 8.8 11.5 11 56 2121 600 25 71 150 (150)
P90K 90 8.8 9.6 9.1 66 2122 600 35 85 146 (150)
P110 110 6.6 7.8 7.5 78 2123 600 50 102 150 (150)
P132 132 4.2 6.5 6.2 96 2124 600 50 124 150 (150)
P160 160 4.2 5.4 5.1 120 2125 600 70 198 150 (150)
P200 200 3.4 4.3 7.8 / 2 = 3.9 2 x 78
2 x 2126
3
*
600 2 x 25 200 150 (150)
P250 250 2.3 3.4 6.6 / 2 = 3.3 2 x 90
2 x 2127
3
*
600 2 x 35 234 150 (150)
P315 315 2.3 2.7 5.4 / 2 = 2.7 2 x 112
2 x 2128
3
*
600 2 x 50 288 150 (150)
Abbreviations for the Tables
*) Resulting max. brake torque when using R
rec
. Using the R
br,nom
will result in maximum brake torque e.g. 160%. The value
in brackets is the drives max. brake torque
2
*) All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
(60/75°C) conductors are recommended.
3
*) Order the specified amount of Brake Resistors (e.g. 2 x 1062 = 2 pieces of 175U1062). See table header for the first four
characters (175U or 130B).
4
*) Rating for each thermistor relay (using one thermistor relay per resistor).
5
*) Parallel star connection (see the Installation chapter).
6
*) Please contact Danfoss for further info.
7
*) With Klixon Switch
P
m
: Rated motor size for VLT type
R
min
: Minimum permissible brake resistor - by drive
R
rec
: Recommended brake resistor (Danfoss)
P
b, max
: Brake resistor rated power as stated by supplier
Therm. relay : Brake current setting of thermal relay
Code number : Order numbers for Danfoss Brake Resistors
Cable cross section : Recommended minimum value based upon PVC insulated copper cable, 30 degree Celsius ambient temperature
with normal heat dissipation
P
pbr,avg
: Brake Resistor average rated power as stages by
R
br,avg
: The nominal (recommended) resistor value to ensure a brake power on motor shaft of 160%/110% for 1 minute
How to Order FC 300 Design Guide
110 MG.33.BD.02 - VLT
®
is a registered Danfoss trademark
55

Table of Contents

Other manuals for Danfoss VLT FC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 and is the answer not in the manual?

Danfoss VLT FC 100 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100
CategoryDC Drives
LanguageEnglish

Related product manuals