EasyManua.ls Logo

Danfoss vlt FC 102 - Basic Programming; Commissioning with Smartstart; Commissioning Via [Main Menu]

Danfoss vlt FC 102
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.4 Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic
motor and application parameters.
At first power-up or after initialization of the
adjustable frequency drive, SmartStart starts by
itself.
Follow on-screen instructions to complete commis-
sioning of the adjustable frequency drive.
SmartStart can always be reactivated by selecting
Quick Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to 5.4.2 Commissioning via [Main Menu]
or the Programming Guide.
NOTICE!
Motor data are required for the SmartStart set-up. The
required data are normally available on the motor
nameplate.
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-up
and checkout purposes. Application settings may vary.
Enter data with power ON, but before operating the
adjustable frequency drive.
1. Press [Main Menu] on the LCP.
2. Use the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A 1 (1)
Main Menu
Figure 5.2 Main Menu
3. Use navigation keys to scroll to parameter group
0-0* Basic Settings and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A 1(1)
130BP087.10
Figure 5.3 Operation/Display
4.
Use navigation keys to scroll to 0-03 Regional
Settings and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A 1(1)
130BP088.10
Figure 5.4 Basic Settings
5.
Use navigation keys to select [0] International or [1]
North America as appropriate and press [OK]. (This
changes the default settings for a number of basic
parameters).
6. Press [Main Menu] on the LCP.
7.
Use the navigation keys to scroll to 0-01 Language.
8. Select language and press [OK].
9. If a jumper wire is in place between control
terminals 12 and 27, leave 5-12 Terminal 27 Digital
Input at factory default. Otherwise, No Operation
should be selected in 5-12 Terminal 27 Digital Input.
For adjustable frequency drives with an optional
bypass, no jumper wire is required between control
terminals 12 and 27.
10.
3-02 Minimum Reference
11.
3-03 Maximum Reference
Commissioning
VLT
®
HVAC Drive Instruction Manual
28 MG11AJ22 - Rev. 2013-09-13
55

Table of Contents

Other manuals for Danfoss vlt FC 102

Related product manuals