8.6 Control Input/Output and Control Data
Digital inputs
Programmable digital inputs 4 (6)
1)
Terminal number 18, 19, 27
1)
, 29
1)
, 32, 33,
Logic PNP or NPN
Voltage level 0–24 V DC
Voltage level, logic'0' PNP <5 V DC
Voltage level, logic'1' PNP >10 V DC
Voltage level, logic '0' NPN
2)
>19 V DC
Voltage level, logic '1' NPN
2)
<14 V DC
Maximum voltage on input 28 V DC
Pulse frequency ranges 0–110 kHz
(Duty cycle) Min. pulse width 4.5 ms
Input resistance, R
i
Approx. 4 kΩ
Safe Torque Off Terminal 37
3, 4)
(Terminal 37 is fixed PNP logic)
Voltage level 0–24 V DC
Voltage level, logic'0' PNP <4 V DC
Voltage level, logic'1' PNP >20 V DC
Maximum voltage on input 28 V DC
Typical input current at 24 V 50 mA rms
Typical input current at 20 V 60 mA rms
Input capacitance 400 nF
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1)
Terminals 27 and 29 can also be programmed as output.
2)
Except Safe Torque Off input Terminal 37.
3)
See for further information about terminal 37 and Safe Torque Off.
4)
When using a contactor with a DC coil inside in combination with Safe Torque Off, it is important to make a return way for the
current from the coil when turning it off. This can be done by using a freewheel diode (or, alternatively, a 30 or 50 V MOV for quicker
response time) across the coil. Typical contactors can be bought with this diode.
Specifications
VLT
®
HVAC Drive Instruction Manual
64 MG11AJ22 - Rev. 2013-09-13
88