Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN 
+10 V
A IN 
A IN 
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB804.10
Function Setting
   
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[19] Freeze
Reference
5-13 Terminal 29
Digital Input
[21] Speed Up
5-14 Terminal 32
Digital Input
[22] Slow
* = Default Value
Notes/comments:
D IN 37 is an option.
Table 6.4 Speed Up/Slow
S t a r t  ( 1 8 ) 
F r e e z e  r e f   ( 2 7 ) 
S p e e d  u p   ( 2 9 ) 
S p e e d  d o w n   ( 3 2 ) 
S p e e d 
R e f e r e n c e 
130BB840.10 
Figure 6.1 Speed Up/Slow
6.1.2
Start/Stop
 
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN 
+10 
A IN 
A IN 
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function Setting
   
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[0] No
operation
5-19 Terminal 37
Safe Stop
[1] Safe Stop
Alarm
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input is
set to [0] No operation, a jumper
wire to terminal 27 is not
needed.
D IN 37 is an option.
Table 6.5 Start/Stop Command with Safe Stop Option
130BB805.11
Speed
Start (18)
Figure 6.2 Start/Stop Command with Safe Stop
Application Set-up Examples
VLT
®
 HVAC Drive Instruction Manual
MG11AJ22 - Rev. 2013-09-13 35
6 6