6.1.5 Motor Thermistor
CAUTION
Use only thermistors with reinforced or double insulation
to meet PELV insulation requirements.
Parameters
130BB686.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Function Setting
1-90 Motor
Thermal
Protection
[2] Thermistor
trip
1-93 Thermistor
Source
[1] Analog
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1] Thermistor
warning.
D IN 37 is an option.
Table 6.10 Motor Thermistor
Application Set-up Examples
VLT
®
HVAC Drive Instruction Manual
38 MG11AJ22 - Rev. 2013-09-13