Type Designation P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
Typical Shaft Output [kW] 5.5 7.5 11 15 18.5 22 30 37 45
Typical Shaft Output [HP] at 208 V 7.5 10 15 20 25 30 40 50 60
IP20/Chassis
7)
B3 B3 B3 B4 B4 C3 C3 C4 C4
IP21/NEMA 1 B1 B1 B1 B2 C1 C1 C1 C2 C2
IP55/Type 12 B1 B1 B1 B2 C1 C1 C1 C2 C2
IP66/NEMA 4X B1 B1 B1 B2 C1 C1 C1 C2 C2
Output current
Continuous (3x200–240 V) [A] 24.2 30.8 46.2 59.4 74.8 88.0 115 143 170
Intermittent (3x200–240 V) [A] 26.6 33.9 50.8 65.3 82.3 96.8 127 157 187
Continuous kVA (208 V AC) [kVA] 8.7 11.1 16.6 21.4 26.9 31.7 41.4 51.5 61.2
Max. input current
Continuous (3x200–240 V) [A] 22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0
Intermittent (3x200–240 V) [A] 24.2 30.8 46.2 59.4 74.8 88.0 114.0 143.0 169.0
Additional Specifications
Estimated power loss at rated max. load
[W] 4)
269 310 447 602 737 845 1140 1353 1636
IP20 max. cable cross-section (line
power, brake, motor and load sharing)
10, 10 (8,8,-) 35,-,-(2,-,-) 35 (2) 50 (1) 150 (300MCM)
IP21, IP55, IP66 max. cable cross-section
(line power, motor) [mm
2
/(AWG)]
10, 10 (8,8,-)
35, 25, 25 (2,
4, 4)
50 (1) 150 (300MCM)
IP21, IP55, IP66 max. cable cross-section
(brake, load sharing) [mm
2
/(AWG)]
16, 10, 16 (6, 8, 6) 35,-,-(2,-,-) 50 (1) 95 (3/0)
Efficiency
3)
0.96 0.96 0.96 0.96 0.96 0.97 0.97 0.97 0.97
Table 8.3 Line Power Supply 3x200–240 V AC - Normal overload 110% for 1 minute, P5K5-P45K
Specifications
VLT
®
HVAC Drive Instruction Manual
54 MG11AJ22 - Rev. 2013-09-13
88