Type Designation P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 11 15 18.5 22 30 37 45 55 75 90
Typical Shaft Output [HP] at 460 V 15 20 25 30 40 50 60 75 100 125
IP20/Chassis
7)
B3 B3 B3 B4 B4 B4 C3 C3 C4 C4
IP21/NEMA 1 B1 B1 B1 B2 B2 C1 C1 C1 C2 C2
IP55/Type 12 B1 B1 B1 B2 B2 C1 C1 C1 C2 C2
IP66/NEMA 4X B1 B1 B1 B2 B2 C1 C1 C1 C2 C2
Output current
Continuous (3x380–439 V) [A] 24 32 37.5 44 61 73 90 106 147 177
Intermittent (3x380–439 V) [A] 26.4 35.2 41.3 48.4 67.1 80.3 99 117 162 195
Continuous (3x440–480 V) [A] 21 27 34 40 52 65 80 105 130 160
Intermittent (3x440–480 V) [A] 23.1 29.7 37.4 44 61.6 71.5 88 116 143 176
Continuous kVA (400 V AC) [kVA] 16.6 22.2 26 30.5 42.3 50.6 62.4 73.4 102 123
Continuous kVA (460 V AC) [kVA] 16.7 21.5 27.1 31.9 41.4 51.8 63.7 83.7 104 128
Max. input current
Continuous (3x380–439 V) [A] 22 29 34 40 55 66 82 96 133 161
Intermittent (3x380–439 V) [A] 24.2 31.9 37.4 44 60.5 72.6 90.2 106 146 177
Continuous (3x440–480 V) [A] 19 25 31 36 47 59 73 95 118 145
Intermittent (3x440–480 V) [A] 20.9 27.5 34.1 39.6 51.7 64.9 80.3 105 130 160
Additional specifications
Estimated power loss
at rated max. load [W]
4)
278 392 465 525 698 739 843 1083 1384 1474
IP20 max. cable cross-section (line
power, brake, motor and load
sharing)
16, 10, - (8, 8, -) 35, -, - (2, -, -) 35 (2) 50 (1) 150 (300 MCM)
IP21, IP55, IP66 max. cable cross-
section (line power, motor) [mm
2
/
(AWG)]
10, 10, 16 (6, 8, 6) 35, 25, 25 (2, 4, 4) 50 (1) 150 (300 MCM)
IP21, IP55, IP66 max. cable cross-
section (brake, load sharing) [mm
2
/
(AWG)]
10, 10, - (8, 8, -) 35, -, - (2, -, -) 50 (1) 95 (3/0)
With line power disconnect switch
included:
16/6 35/2 35/2 70/3/0
185/
kcmil350
Efficiency
3)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.99
Table 8.5 Line Power Supply 3x380–480 V AC - Normal overload 110% for 1 minute, P11K-P90K
Specifications
VLT
®
HVAC Drive Instruction Manual
56 MG11AJ22 - Rev. 2013-09-13