Operation
62
6.4.3 ENGINE RUNNING
Once the engine is running and all starting timers have expired, the animated Engine
Running
icon is displayed
.
In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources.
Activation of an auxiliary input that has been configured to Remote Start On Load or Auxiliary
Mains Fail.
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
Once the generator has been placed on load, it is not automatically removed. To manually remove
the load either:
Press the Auto Mode
button to return to automatic mode. The set observes all auto mode
start requests and stopping timers before beginning the Auto Mode Stopping Sequence.
Press the Stop/Reset Mode button to remove load and stop the generator.
Activation of an auxiliary input that has been configured to Generator Load Inhibit.
6.4.4 STOPPING SEQUENCE
In manual/start mode the set will continue to run until either :
The Stop/Reset Mode
button is pressed – The delayed load outputs are de-activated
immediately and the set immediately stops.
The Auto Mode
button is pressed. The set observes all auto mode start requests and
stopping timers before beginning the Auto Mode Stopping Sequence.