Commissioning - Fault Finding
86
9.6 MISCELLANEOUS
Symptom Possible Remedy
Module appears to ‘revert’ to
an earlier configuration
When editing a configuration using the PC software it is vital that the
configuration is first ‘read’ from the controller before editing it. This
edited configuration must then be “written” back to the controller for
the changes to take effect.
When editing a configuration using the fascia editor, be sure to press
the the Auto Mode
() button to save the change before moving
to another item or exiting the fascia editor
NOTE: The above fault finding is provided as a guide check-list only. As the module can
be configured to provide a wide range of different features, always refer to the source of your
module configuration if in doubt.