Edit Configuration - Inputs
28
Smoke limit
IEEE 37.2 – 18 accelerating or
decelerating device
This input instructs the module to give a
command to
the engine either via an output configured to smoke limit or by data
commands when used with supported electronic engines.
Start Pause
IEEE 37.2 - 3 checking or
interlocking relay
This input is intended to be used to allow the generator start sequence
to commence, but not to complete. This feature can be used with Air
start engines for example to give a controlled start sequence.
The function operates such that if the ‘Start pause’ input is active and
an engine start is commanded, the module will perform its start
sequence thus: -
The pre-heat output (if used) will be activated for the duration of the pre-
heat timer.
The Fuel output will then be energised and the module will then enter a
pause state - ‘Awaiting clear to start’. If the ‘start pause’ signal becomes
inactive at this time then the module will continue its normal start
sequence.
The ‘start pause’ mode uses the ‘manual crank limit’ timer and if this
expires during the ‘Awaiting clear to start’ state then a ‘Fail to start’
alarm will be generated and the set shutdown.
Stop and Panel Lock
Combined function input that instructs the module to enter
MODE and also perform the Panel Lock function.
Once the input is active, the module will not respond to operation of the
Mode select or start buttons.
The operator will still be able to view the various instrumentation pages
etc. (Front panel configuration access is still possible while the system
lock is active).