Load sharing/NO RAMP
This diagram shows how the load balances after breaker closing when the ramp function (in load sharing
mode) is deactivated. The load is balanced immediately, followed by load sharing between the two DGs.
Load sharing/RAMP UP FUNCTION
This diagram shows a situation after the breaker closes and where the ramp function is activated. When DG 2
synchronises, it loads up following the ramp curve. Any variations in load will in principle be taken by DG 1,
until the ramp sequence has ended.
In this diagram, no delay point is used (timer 2143 = 0 s).