EasyManua.ls Logo

Deif GPC-3 - Setup of Step-Up Transformer and Measurement Transformer

Deif GPC-3
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.20.3 Setup of step-up transformer and measurement transformer
If the HV side of the transformer is transforming the voltage up to a voltage level higher than 690 V AC, it will
be necessary with measurement transformers. The setup of all these parameters can be done from the utility
software, and will be explained by an example:
Controller
G
Busbar 10 kV
Dz4
10/0.4 kV
Measurement
transformer
10/0.1 kV
Current transformer
300/5 A
U
GEN
= 400 V
I
GEN
= 250 A
400 V AC
direct input
The transformer is a Dz4 step-up transformer, with nominal settings of 10/0.4 kV.
The generator has a nominal voltage of 0.4 kV, nominal current of 250 A, and a nominal power of 140 kW.
The measurement transformer has a nominal voltage of 10/0.1 kV, and no phase angle twist.
The nominal voltage of the busbar (BB) is 10 kV.
Because the generator’s nominal voltage is 400 V, there is no need for a measurement transformer on the LV
side in this example. The ML-2 can handle up to 690 V. But it is still required to set up current transformers on
the LV side. In this example, the current transformers have a nominal current of 300/5 A.
Due to the fact that the step-up transformer is a Dz4, there will be a phase angle twist of -120 °.
These settings can be programmed via the display or the utility software. These settings must be put into the
parameters shown in the table below:
GPC-3 DRH 4189340587 UK
Additional functions
DEIF A/S Page 89 of 122

Table of Contents

Other manuals for Deif GPC-3

Related product manuals