Connections:
1L1
1L2
1L3
Generator
2L1
2L2
2L3
AGC 3/ AGC 4/ PPU/
GPU/ PPM/ GPC
AGC 200
79
61
81
63
83
65
85
68
87
70
89
72
Busbar
GB
LV HV
The connection shown in the diagram should always be used when an ML-2 is used for a gen-
set.
Vector group 1
The phase shift is -30 degrees.
Dy1 example:
LV (generator) side
2L1
2L2
2L3
1L1
1L21L3
HV side
1L1 to 2L1 phase angle is -30 degrees.
Phase compensation setting:
Parameter Function Setting
9141 BB (mains)/generator angle compensation 30 degrees
GPC-3 DRH 4189340587 UK Additional functions
DEIF A/S Page 84 of 122