If a step-down transformer and an ML-2 for the mains breaker are mounted, note how the measurements are
mounted on the ML-2. The correct connection is shown below.
2L1
2L2
2L3
Mains
1L1
1L2
1L3
AGC 3/ AGC 4/ PPU/
GPU/ PPM/ GPC
AGC 200
79
61
81
63
83
65
85
68
87
70
89
72
Busbar
OptionalLoad
TB
MB
HV
LV
The connection shown in the picture should always be used when an ML-2 is used for a mains
breaker.