These settings can be programmed via the display or the utility software. These settings must be put into the
parameters shown in the table below:
Parameter Comment Setting
6002 Generator nominal power 480
6003 Generator nominal current 500
6004 Generator nominal voltage 690
6041 HV measurement transformer primary side (There is none here) 690
6042 HV measurement transformer secondary side (There is none here) 690
6043 Current transformer primary side 500
6044 Current transformer secondary side 1
6051 LV (BB) measurement transformer primary side (There is none here) 400
6052 LV (BB) measurement transformer secondary side (There is none here) 400
6053 Nominal LV setting of step-up transformer 400
9141 Phase angle compensation -30 °
GPC-3 DRH 4189340587 UK Additional functions